SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES
·······································
2
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 5
4. OUTLINES AND DIMENSIONS ························ 6
5. WIRING DIAGRAM ············································ 7
6. REFRIGERANT SYSTEM DIAGRAM ··············· 9
7. SERVICE FUNCTIONS ··································· 10
8. MICROPROCESSOR CONTROL ··················· 12
9. TROUBLESHOOTING ····································· 22
10. DISASSEMBLY INSTRUCTIONS ···················· 36
MSZ-FE09NA
MSZ-FE12NA
MSZ-FE18NA
SPLIT-TYPE AIR CONDITIONERS
INDOOR UNIT
Outdoor unit service manual
MUZ-FENA Series (OBH543)
MXZ-A·NA Series (OB444)
MXZ-B·NA Series (OB560)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
PARTS CATALOG (OBB542)
Models
MSZ-FE09NA
MSZ-FE12NA
No. OBH542
REVISED EDITION-B
MSZ-FE09NA -
8
MSZ-FE12NA -
8
Revision B:
• MSZ-FE09NA -
8
and MSZ-FE12NA -
8
have
been added.
Please void OBH542 REVISED EDITION-A.
Vista de página 0
1 2 3 4 5 6 ... 43 44

Resumo do Conteúdo

Página 1 - MSZ-FE12NA

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES·······································22. PART NAMES AND FUNCTIONS ····················· 33. SPECIFICATION

Página 2 - TECHNICAL CHANGES

107-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board. The time wi

Página 3 - PART NAMES AND FUNCTIONS

11NOTE:• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller.• If main powe

Página 4 - ACCESSORIES

12Signal transmitting sectionOperation display sectionOPERATE/STOP (ON/OFF) buttonFAN SPEED CONTROL buttonOPERATION SELECT buttonPOWERFUL buttonIndica

Página 5 - SPECIFICATION

138-1. COOL ( ) OPERATION(1) Press OPERATE/STOP (ON/OFF) button. POWER lamp (MSZ-FE09/12NA)/OPERATION INDICATOR lamp (MSZ-FE18NA) of the indoor uni

Página 6 - OUTLINES AND DIMENSIONS

148-3. HEAT ( ) OPERATION(1) Press OPERATE/STOP (ON/OFF) button. POWER lamp (MSZ-FE09/12NA)/OPERATION INDICATOR lamp (MSZ-FE18NA) of the indoor unit

Página 7 - WIRING DIAGRAM

158-5. AUTO VANE OPERATION1. Horizontal vane(1) Vane motor drive These models are equipped with a stepping motor for the horizontal vane. The rotatin

Página 8 - MSZ-FE12NA

16(8) Cold air prevention in HEAT operationThe horizontal vane position is set to Upward.NOTE: When 2 or more indoor units are operated with multi out

Página 9 - REFRIGERANT SYSTEM DIAGRAM

178-6. i-see CONTROL OPERATION (MSZ-FE09NA MSZ-FE12NA)The sensors constantly measure the room and floor/wall temperatures to automatically adjust to

Página 10 - SERVICE FUNCTIONS

18Indoor unit installation location and air-conditioning area·Be sure to set the slide switch inside the remote controller to an appropriate position

Página 11 - Position of

19Operation and operating rangei-see sensor moves 30 degrees from the center in both right and left side.i-see Sensor operates as follows in accordanc

Página 12 - MICROPROCESSOR CONTROL

21TECHNICAL CHANGESMSZ-FE09NAMSZ-FE12NAMSZ-FE18NA 1. New modelRevision A:• MSZ-FE18NA has been added.Use the specifi ed refrigerant onlyNever use any

Página 13 - INDOOR UNIT DISPLAY SECTION

20(Example 1) The current time is 8:00 PM.The unit turns off at 11:00 PM, and on at 6:00 AM.• OFF timer and ON timer can be used in combination. The t

Página 14

218-11. Changing temperature indication (°F/°C)8-10. 3-MINUTE TIME DELAY OPERATIONWhen the system turns OFF, compressor will not restart for 3 minutes

Página 15 - Horizontal

229-1. CAUTIONS ON TROUBLESHOOTING1. Before troubleshooting, check the following1) Check the power supply voltage.2) Check the indoor/outdoor connecti

Página 16 - (MSZ-FE18NA)

23Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the tro

Página 17

242. Indoor unit failure mode tablePOWER lampUpper lampAbnormal point (Failure mode) Condition RemedyNot lighted Normal — —1-time fl ash every 0.5-se

Página 18 - Not lighted

25Indoor unit oper-ates.Outdoor unit does not operate.If blinking of OPERATION INDI-CATOR lamp cannot be checked, it can be checked with failure mode

Página 19

269-4. TROUBLESHOOTING CHECK TABLEBefore taking measures, make sure that the symptom reappears for accurate troubleshooting.When the indoor unit has s

Página 20

27 L AREA R POWER No. Abnormal point Operation indicator lamp Symptom Condition Remedy1MXZ type Operation mode settingMSZ-FE09/12NAPOWER

Página 21

289-6. TROUBLESHOOTING FLOW A Check of indoor fan motorThe indoor fan motor error has occurred, and the indoor fan does not operate.Turn OFF the powe

Página 22 - TROUBLESHOOTING

29 B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner.Does th

Página 23

3PART NAMES AND FUNCTIONS2MSZ-FE09NA MSZ-FE12NAFront panelAir filterAir inletOperation indicator lampPlatinum deodorizing filterAnti-allergy Enzyme Fil

Página 24 - Upper lamp: MSZ-FE18NA

30 C Check of indoor electronic control P.C. board and indoor fan motorTurn OFF the power supply.Remove indoor fan motor connector CN211, vane motor

Página 25

31CN211R111Indoor electroniccontrol P.C. boardIndoor terminalP.C. boardFuse(F11)Varistor(NR11)YesNo 1. The fan motor connector's lead wire i

Página 26 - Blinking

32 D How to check miswiring and serial signal errorTurn OFF inverter-controlled lighting equipment.Turn OFF the power supply and then turn ON again.P

Página 27 - Abnormal

33 E Electromagnetic noise enters into TV sets or radiosYesIs the unit grounded?NoGround the unit.YesIs the distance between the antennas and the ind

Página 28 - A Check of indoor fan motor

34MSZ-FE09NA MSZ-FE12NA1. Indoor electronic control P.C. board9-7. TEST POINT DIAGRAM AND VOLTAGERoom temperature thermistor (RT11)Indoor coil thermi

Página 29 - MSZ-FE18NA

354. Indoor terminal P.C. board, Indoor electronic control P.C. board, Power monitor receiver SW P.C. boardRoom temperature thermistor (RT11)Indoor co

Página 30

3610-1. MSZ-FE09NA MSZ-FE12NANOTE: Turn OFF power supply before disassembly.OPERATING PROCEDUREPHOTOS1. Removing the panel(1) Hold both sides of the

Página 31

37OPERATING PROCEDUREPHOTOS2. Removing the electronic control P.C. board, the power monitor receiver P.C. board, i-see Sensor, SW P.C. board and the t

Página 32

38OPERATING PROCEDUREPHOTOS3. Removing the electrical box(1) Remove the panel (Refer to 1.) and the corner box.(2) Remove the indoor/outdoor connectin

Página 33

39OPERATING PROCEDUREPHOTOS6. Removing the horizontal vane motor(1) Remove the nozzle assembly. (Refer to 4.)(2) Remove the screws of the horizontal v

Página 34

4Remote controller Display sectionFront panelAir filter(Nano platinum filter)Air inletAir cleaning filter(Electrostatic anti-alergy enzyme filter)Air

Página 35 - Resistance (kΩ)

4010-2. MSZ-FE18NANOTE: Turn OFF power supply before disassembly.OPERATING PROCEDURE PHOTOS1. Removing the panel(1) Remove the horizontal vanes.(2) Re

Página 36 - DISASSEMBLY INSTRUCTIONS

41OPERATING PROCEDURE PHOTOS3. Removing the indoor electrical box(1) Remove the panel (Refer to 1.) and the corner box.(2) Remove the indoor/outdoor c

Página 37 - OPERATING PROCEDURE

42OPERATING PROCEDURE PHOTOS5. Removing the vertical vane motor unit(1) Remove the nozzle assembly. (Refer to 4.)(2) Remove the crank of the vertical

Página 38

43OPERATING PROCEDURE PHOTOS7. Removing the water cut, the indoor fan motor, the indoor coil thermistor, and the line flow fan(1) Remove the panel (Re

Página 39

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN© Copyright 2009 MITSUBISHI ELECTRIC CO., LTDDistributed in Apr. 2011.

Página 40 - OPERATING PROCEDURE PHOTOS

53SPECIFICATIONIndoor modelMSZ-FE09NA MSZ-FE12NA MSZ-FE18NAPower supply V, phase, Hz 208/230 , 1 , 60Max. fuse size (time delay)/ Disconnect switchA15

Página 41

64OUTLINES AND DIMENSIONSUnit: inchMSZ-FE09NA MSZ-FE12NA30-7/831-3/81/21-7/82-3/1611-5/827-1/163/42-5/166-1/41-11/162-11/162-3/163-15/161/210-1/8 1/4

Página 42

75WIRING DIAGRAMMSZ-FE09NA MSZ-FE12NA

Página 43

8MSZ-FE18NAMSZ-FE09NA - 8 MSZ-FE12NA - 8

Página 44

9MSZ-FE09NA MSZ-FE12NARefrigerant flow in coolingRefrigerant flow in heatingUnit: inchIndoorheatexchangerFlared connectionRoom temperaturethermistorR